No cool. Found condenser not running where thermostat was set to cool. 87° upon arrival. Went to outdoor unit compressor and fan off on internal overload used water hose to cool down compressor and motor. Run capacitor rated at 55+5 was dead. Installed New turbo 200 run capacitor. Part has five year warranty. .Turn the unit back on and checked charge. Added 4 pounds of our 22. Checked amp draw on motor and fan. Compressor pulling 14 A, fan pulling 1.2 A. Turned on other system just to verify that it is operating properly. Both systems are cooling at this time.