Leak search on kitchen unit. Pump down system to isolate the refrigerant in the condenser. Soaked condenser coil with bubbles. Found nothing on the condenser. Soap bubbled the condenser compressor. Found nothing. Compressor in this unit has been changed out before. When I started the system back up the head pressure or the condenser coil pressure was higher than it should’ve been. I gave the condenser coil of chemical bath. Rinsed coil completely clean. Pressures remain the same. Head pressure was 475 psi. Suction line temperature is 55° and indoor temperature of the kitchen is 72°. No leaks were found today. Recommendation today given the age of the system and the pressures is to change out system.