Post install walkthrough on recently installed equipment. Verified and cleared primary drain and it is Flowing properly now. Check outdoor unit. Refrigerant level is good at this time. T stat being blank was due to the inline float switch interrupting power because the drain was clogged. System is working at manufacture specs at this time. I left and 8:50 thermostat because Kevin wanted to have his original thermostat until it no longer worked.