Compressor is about to lock up. Amps are close to locked rotor amps. Needs new Compressor. 10 ton system need a 7/8" liquid line dryer with valve ports. Compressor is running 10 amps . Information late is completely covered. Not sure how much 410A system holds. Need to look that up before giving price on recharge of system. LRA is 35.5 and compressor is at 28.3 rla 3 phase system. Not running in reverse. I checked that first thing. 10/8/21 Replaced Compressor and installed liquid line drier and suction line drier. Suction line drier to be removed at a later date. To be scheduled. Line drier are not listed so took pictures of part numbers . Leak checked system with nitrogen and then vacuumed down to 241 microns. System now working properly 1" static pressure Put in compressor numbers can't add to materials. Not listed.