Cliff P.

Cliff P.


Job Checkin

Repair shorted out low voltage wire to overflow kill switch and repaired thermostat wire at outdoor unit. Changed out a week run capacitor for the blower motor and cleared the drain line and treated the drain pan with an antimicrobial agent. Replaced blown fuse caused by low voltage short. Outdoor capacitor is fine. Compressor is pulling High amps 10.6/15.4 and fan amp draw is 1.2/1.3, amp draw could possibly be reduced with cleaner coils. Recommend a checkup. System is running, cooling, and draining fine.