Customer called due to system not operating when I arrived systems thermostat was set for cooling but unit was not coming on. Found system to have a blown 5 amp fuse. Replaced fuse tried starting system up unit would come on but condenser would shut off then try to start again this happened multiple times before blowing 5 amp fuse again. Bypassed thermostat and tried starting system again with new fuse system immediately had blown fuse. Disconnected contactor at condenser and replaced fuse again started system back up system started fine and did not blow fuse. Replaced contactor and wired thermostat back up systems condenser fan motor would continue to run due to defective condenser defrost board bypassed fan from board. Started system up in cooling checked system operations all ok. System is operating correctly at this time. Recommend system replacement over major Repairs due to age and condition. System has a defective defrost board brought to customers attention. Recommend maintenan