Customer stated that indoor breaker Head trip was able to reset and get unit running found outdoor disconnect wires very loose possible causing breaker to overheat and trip. Ran and check the unit compressor had slightly high amp draw. Replaced with new dual run capacitor due to compressor side of capacitor reading 36 microfarads rated at 45. Customers under carrier parts and labor warranty. Unit is operating normally at this time