FOUND UNIT COMPLETELY OUT OF REFRIGERANT. STATIC CHARGE WITH NITROGEN. FOUND LEAK AT SUCTION LINE WHERE ROOFING NAIL PENETRATED COPPER LINE. REPAIRED LEAK . VACCUMED TO 410 MICRONS. RECHARGED WITH NEW R410. UNIT IS COOLING NORMALLY AT THIS TIME.