8021 W. Gulf to Lake Hwy
Crystal River , FL 34429
352 795 2665

Job Locations
for inglis, fl


Map of Inglis FL
Robert H.

Robert H.


Job Checkin

Check unit system has a 20 degree split and is running very hard 98 degrees outside. Replace dual run capacitor. Rated 70 microfarads + 10 microfarad was reading 70 + 7. Outdoor fan motor amp draw was not high. Replace capacitor head pressure drop slightly system is Cooling and draining fine at this time