Job Checkin

All capacitor are in good shape. Compressor is pulling 7.6/18.3 amps and the fan is pulling .6/.7 amps. Both are in good shape. Condensing coil is nice and clean. Evaporator coil is a bit dirty but not hindering cooling. Could use a coil pull and clean to optimize performance and improve dehumidification. One coil pull and clean and good filter maintenance will ensure evaporator coil stays clean. Left estimate for this procedure. Refrigerant circuit is in good shape with the appropriate charge. Overall unit seems to be in very good shape. Unit is running, cooling, and draining fine.