Cliff P.

Cliff P.


Job Checkin

System operating normally. Charge looks good, superheat and subcool do as well. Compressor amp draw 10.1/16 and condensing fan pulling 1.3/1.5. System is draining well and the drain pan is clean. Replaced failed float switch. Unit is doing fine at this time.