System had weak capacitor and hard start, changed both. Attempted to run unit but low voltage would not engage contactor. Tabbed through every possibility and determined the contactor, incoming voltage, and all safety devices are good. Bypassed the board and the unit is running and cooling fine. Compressor has an amp draw of 8.7/16.64. Pressures and temperatures look good as well. Filing out part quote request form to see if customer is interested in replacement of the board. Customer is interested in check up by technician 477 asap.