3 ton system, (strt cool) Improper tstat, (heat pump) Noisey breaker identified as for Indoor Unit (30a with #10 wire) Indoor unit with heat on draws 33amps, the breaker in question is going into failure, breaker panel appears to be a 60 panel, tenant has been instructed to NOT USE heat until electrician is on property