upon arrival the condenser would not start. I found float switch wet and slime in drainline. The float is wired to shutdown condenser only. I added drainsolve to drainline. Then I flushed multiple times with water. The slime came out and is draining freely now. I checked refrigerant pressures and were fine. 140 suction and 300 head.