Unit 1 Check t/start change filter check blower motor flush condensate drain. Supply air 48 return air 67. Check disconnect two 20 amps Fuse. Check capacitor 30+5+440 Dual Run Cap. Check contactor Cycled unit on to check fan motor and compressor working. Wash and clean outdoor coil. Outdoor temperature is 58°. At time of dispatch unit is working. Unit 2 Check t/state change filter check blower motor flush condensate drain. Supply air 50* return air 66*. Check disconnect two 20 amps fuse. Checked capacitor 30+5+440 Dual Run Cap. Check contactor cycle unit on to check compressor and fan working . Wash and clean condenser coil. Outdoor temperature 59*. At times of dispatch unit is working.