Preformed furnace C&T. Pulled out, inspected and cleaned burners, reinstalled. Ohmed out igniter, working well at this time. Inspected outer compartment of heat exchanger and saw rust. Scrubbed rust off with wire brush. Removed and cleaned flame sensor, reinstalled.. checked filter, 201 filter. Checked and inspected gas outlet, adjusted pressure to 3.5. Avg life expectancy for this furnace is 14 years. This system is 22 years old. Future failure is expected. Inspected blower mtr, circuit board, blower box. Tested safety systems and all worked well at this time. Complete