Furnace clean and tune. Cycled system. Checked heat exchanger, found several rust spots and deep etching in both shots. Found igniter cracked. Igniter broke while removing it from burner box, replaced with new. Found burners very rusted and damaged. Ventor motor bearings are worn and noisy. Transition assembly is leaking. Found no CO in airstream. Higher levels of XS air in exhaust. Normal levels of CO in exhaust, higher, but normal at this time. Possible blockage in secondary heat exchanger. Large amount of water leaking into blower compartment causing water to leak from cabinet. Water appears to be coming from secondary and transition assembly. Drain lines are in very poor condition. Looks as though someone replaced some at an earlier point causing water to leak. Average life of this system is 14 years. This system is over 20 years old and in very poor condition. Second opinion recommended. Job complete.