Job Checkin

The new air conditioner wasn’t keeping up during the day. I cycled the air conditioner and checked the charge. Found the condenser coil was plugged with cottonwood. I washed the condenser coil. Checked the charge. It was low on charge. I added a pound of refrigerant to get the proper charge. I checked the split, it was at 19. Checked the air handler. Found the sensing bulb wasn’t insulated. I insulted it. The air conditioner is cooling properly at this time. We need to come back to adjusted the lineset in the attic. Office will call to schedule that.