Came out to investigate a no heat. The pressure switch was stuck open. I cleared all moisture from the drain lines and the pressure hoses with no success for ignition. I tested the water column and I had 2” and the switches themselves are rated for 0.70” and 0.20”. Pressure switches will need to be replaced. We will return when we have them at collect the payment.