Propane Furnace 1 1998 Completed tune up and clean System has 2006 heat exchanger Inducer motor hits max amp on start up Recommend replacement inducer. Furnace 2 1998 Comfortmaker mn: ntg9075fgaz. Sn: L982750620 Customer complaint was that the furnace would shutdown: Photos are of rogue flame in burner box. The gas burners are disintegrating and flame is hitting the burner box, excessive burning on instead of chamber. Inducer motor is running past max capacity, will fail soon System is unsafe to run as is as carbon monoxide risk is high Recommended parts need to be replaced: Gas burners Metal shield in burner box Burner box Rollback limit switch (weak from extended use) Also Inducer motor C&t was not preformed on furnace 2 Dan Fox to do second opinion. I have done a show and tell with mrs homeowner through issues No money taken by Gary.