Job Checkin

Performed the level 2 package cleaning. Furnace: Burners and flame sensor are clean. Heat exchanger looks good. Combustion readings were normal. No CO detected in the air. Drain is clear. Inducer motor had excessive moisture that was causing it to not run at full capacity. We cleared out the moisture and everything is running properly. AC: No leaks detected. Electrical components tested good. Condenser coil is clean. Refrigerant charge was normal. Subcool was 9° with a 17° temp split. All equipment is operating properly.