Hunter D.

Hunter D.


Job Checkin

Performed the level 2 furnace cleaning. Burners and flame sensor are clean. Heat exchanger looks good. Combustion readings were normal. No CO detected in the air. Drain is clear. High limit passed the safety check. Heat rise was 53°. Unit is heating properly. We will call in the spring to schedule the AC cleaning.