Performed the level 2 furnace cleaning. Burners and flame sensor are clean. Heat exchanger looks good. Gas and exhaust levels are normal. No CO detected in the air. Drain is clear. Heat rise was 42 degrees. Unit is heating properly at this time. There is a moisture stain on top of the unit. I didn’t find any signs of water damage or rust in the furnace or any leaks in the surrounding area. Pictures were uploaded. Looks like water came from the fresh air pvc so I tightened the pipe a little more.