Inoperable Deficiency for Scotsman MDT5N40A-1J BHM00798 11021320012394 3rd Floor Break Room: Arrived to do pm of break room equipMeant. I was escorted to 3rd floor and found ice machine off. Customer informed me that no one has been in the office for 3 months. I found the unit not receiving power. Checked receptacle and I had zero volts. Could not access electrical closet at this time. Customer didn’t have access. Inoperable Deficiency for Break room BHM07564 Frigidaire Fccm201rfb2 Wa11903350: Arrived to complete pm. Customer informed me that unit has been off for 3 months with door open. I turned it on and only the light comes on. I received and okay to investigate and verified incoming power at receptacle. The thermostat was set to off and once I set to 7 (out of 10) nothing came on. Checked voltage to compressor (0 volts), checked voltage to evaporator fan (0). It appears at this time that the thermostat in the evaporator needs replaced due to failure. I advised customer and she