System- single system Approx Age of System: 5 Refrigerant Type- R410a Metering Device- TXV SP/HP: 115/276.9 SLT/LLT: 62.8/80.9 VSAT/LSAT- 38.3/90.4 Superheat/Subcool- 24.2/9 Outdoor Entering Air Temp- 76.1 Outdoor Fan FLA- .4 Compressor RLA/LRA- 7.4/82.3 Contactor Voltage- 245.4 Capacitor Rating- 41/2 Indoor Return Dry Bulb Temp-69.8 Return wet bulb- 43.7 Supply Temp- 55.5 Temperature Difference- 14.3 Required Difference- 16-20 Blower FLA- 5.70 Static- return .3 supply .4 Filter Sizes –20x25x4 Changed Filters – Y Blew out drain line: N Notes- no service valve to blow out drain line. Condenser capacitor should be a value of 45/5mfd +-5% it is far bellow recommended value and is causing strain on the systems components. Maximum inrush amps tested and recommend by the manufacturer is 72amps At this time system is pulling 82.3amps straining the compressor and other system components. Comfort advisor to come out Wednesday between 12p.m. To 1p.m. Next Scheduled Tune up Date: wi