Job Checkin

System-1 system Approx Age of System: 10 years old Refrigerant Type- R410a Metering Device- TXV SP/HP:112/263 SLT/LLT:50/78 VSAT/LSAT- 36/86 Superheat/Subcool-13.4/8.3 Outdoor Entering Air Temp-83 Outdoor Fan FLA- 1.20 Compressor RLA/LRA-14.2/158.8. Rated 134.0 Contactor Voltage-242 Capacitor Rating-73.9/7.5 Indoor Return Dry Bulb Temp-73 Return Wet Bulb Temp-63 Supply Temp- 54 Temperature Difference-19 Required Difference-15-20 Blower FLA- 3.6 Filter Sizes – 20x25x1 Changed Filters – No (clean) Blew out drain line: Yes Notes- Condenser is drawing high amperage upon start up, would recommend compressor saver to reduce strain on equipment and reduce amp draw on start up. Customer is going to consider recommendation. Scheduled next tune up date: 11/2/20 10-2