Henry M.

Henry M.


Job Checkin

System-Bryant Approx Age of System:2 Refrigerant Type- R410a Metering Device- TXV SP/HP:117.5/212.7 SLT/LLT:54.7/65.6 VSAT/LSAT- 39.5/72.8 Superheat/Subcool-14.9/7.5 Outdoor Entering Air Temp-64 Outdoor Fan FLA- .5 Compressor RLA/LRA-8.6/ Contactor Voltage-243.5/27.1 Capacitor Rating-44.2/7.31 Indoor Return Dry Bulb Temp-69.7 Return Wet Bulb Temp-60.8 Supply Temp- 54.5 Temperature Difference-15 Required Difference-16-20 Blower FLA- 4,43 Filter Sizes –20x30x1 Changed Filters – Y Blew out drain line: Y Notes-Upon arrival for a/c tuneup, checked in with Mr.Chambers and located hvac equipment. Made the call for cooling and proper operation followed. At the outdoor unit refrigerant pressures and electrical readings were within manufacture specifications. The compressor was pulling high amps upon