System- single system Approx Age of System: furnace 19 condenser/evaporator coil 18 Refrigerant Type- R22 Metering Device- TXV SP/HP: 66.3/249.5 SLT/LLT: 60.7/106.7 VSAT/LSAT- 38.5/117 Superheat/Subcool- 22.2/10.3 Outdoor Entering Air Temp- 95 Outdoor Fan FLA- .9 Compressor RLA/LRA- 22.1/177.8 (high energy draws on start up) Contactor Voltage- 241/240.9 (potential for failure) Capacitor Rating- 66/3 (Very low value high risk of failure in the future) Indoor Return Dry Bulb Temp- 74.8 Return Wet Bulb Temp- 46.3 Supply Temp- 56.7 Temperature Difference- 18.1 Required Difference- 16-20 Blower FLA- 7.2 Filter Sizes – 20x25x4 Changed Filters – Y (customer supplied) Blew out drain line: N (No service valve to blow out drain line) Returned tstat to original settings: Y Unit operational; prior to leaving: Y Notes- provided an estimate for multiple repairs and ways to maintain the system, highly suggest replacing the equipment due to age and condition. Static pr