Arrived on site, called Judy and met with Walter, found that the condenser fan motor was bad. Customer wanted motor changed. Replaced the motor started the system and found it to be low on charge. Got approval to add refrigerant, added 2 lbs of R22. System is operating within specifications. System-Main Approx Age of System: 16 Type- R22 Metering Device-Txv SP/HP:81.1/293.4 SLT/LLT:71.2/120.5 VSAT/LSAT- 48.2/129.1 Superheat/Subcool-23/8.6 Outdoor Entering Air Temp-91