Ken P.

Ken P.


Job Checkin

System- main Approx Age of System: 2 Refrigerant Type- R410a Metering Device- TXV SP/HP: 128/338 SLT/LLT: 55/95 VSAT/LSAT- 44/104 Superheat/Subcool- 10/9 Outdoor Entering Air Temp- 84 Outdoor Fan FLA- 1.17 Compressor RLA/LRA- 13.4 Contactor Voltage- 239 Capacitor Rating- 24/0.74 of 45/5 Indoor Return Dry Bulb Temp- 75 Return Wet Bulb Temp- 66 Supply Temp- 55 Temperature Difference- 20 Required Difference- 15-22 Blower FLA- 5.7 Filter Sizes – 20x25x1, 12x24x1, 12x12x1 Changed Filters – N Blew out drain line: Y Returned tstat to original settings: Y Unit operational; prior to leaving: Y Notes- Performed AC tune up, replaced UV lamp and checked system and ducting for organic growth. There was no organic growth in the unit or in the visible ducting. The capacitor had failed, Mrs. Lemaire approved replacement of the capacitor. There was also water in the pan dripping from the suction line, I re-insulated the suction to prevent it from condensating, and dried tha