Ronald  E.

Ronald E.


Job Checkin

Heat Tune-up System:Main Age of System: 9 Combustible Gas Leak Detection Pipe and fittings leak-free: yes Valves and orifices leak-free: yes Carbon Monoxide Testing Walk-around CO: pass / 0 ppm Airside CO: pass /return 0 ppm supply 0 ppm Flue gas carbon monoxide: pass/ 18 ppm Ignition and Combustion Delayed ignition: yes Flame disturbance: yes Flame discoloration: yes Motor Amperages and Capacitors Blower motor FLA: 5.38 Induced draft/combustion blower motor FLA: 1.27 Capacitor(s): pass 7.5mfd Temperature Rise Rated: 1st 30-60 Actual: 1st 48 Static Pressures Blower speed/cfm: /FR .38 /FS /SP TESP: n/a Safety Controls Primary limit test: pass Filter sizes: 20x25x4 Changed filters: No Notes: performed heat tune up x1, checked unit for proper operations no heating issues were visible, proper electrical connections, free of any gas leaks, free of any CO leaks, proper ignition and combustion. Unit has properly installed gas flex connector and s