System- upstairs Approx Age of System: 18 Refrigerant Type- R22 Metering Device- Fixed Orifice SP/HP: 64.7/153 SLT/LLT: 58.8/84.4 VSAT/LSAT- 38.4/83.9 Superheat/Subcool- 20/2 Outdoor Entering Air Temp- 70 Outdoor Fan FLA- .98 Compressor RLA/LRA- 5.47 Contactor Voltage- 241/24 Capacitor Rating- 40/5 Indoor Return Dry Bulb Temp- 69 Return Wet Bulb Temp- Supply Temp- 54 Temperature Difference- 15 Required Difference- 15-20 Blower FLA- 5.44 Filter Sizes – 20x20x1 Changed Filters – customer will replace Blew out drain line: N _____________________________________________________ System- downstairs Approx Age of System: 18 Refrigerant Type- R22 Metering Device- Fixed Orifice /TXV SP/HP: 56.9/174 SLT/LLT: 61.9/83.1 VSAT/LSAT- 31.8/92.1 Superheat/Subcool- 28/8.9 Outdoor Entering Air Temp- Outdoor Fan FLA- .64 Compressor RLA/LRA- 8.30 Contactor Voltage- 240/24 Capacitor Rating- 40/5 Indoor Return Dry Bulb Temp- 68 Return Wet Bulb Temp- Supp