30045 FM 2978 Rd.
Magnolia, TX 77354
(281) 651-5484

Job Locations
for houston, tx


Map of Houston TX
Ronald  E.

Ronald E.


Job Checkin

System- main Approx Age of System: 2 Refrigerant Type- R410a Metering Device- TXV SP/HP: 120.3/262.0 SLT/LLT: 53.7/80.2 VSAT/LSAT- 40.8/86.5 Superheat/Subcool- 12.7/6.3 Outdoor Entering Air Temp- 71 Outdoor Fan FLA- 1.28 Compressor RLA/LRA- 8.40/98.8 Contactor Voltage- 248/27 Capacitor Rating- 45/10 Indoor Return Dry Bulb Temp- 70 Return Wet Bulb Temp- Supply Temp- 52 Temperature Difference- 18 Required Difference- 15-20 Blower FLA- 4.86 Filter Sizes – 20x25x4 Changed Filters – Clean Blew out drain line: N Notes- performed ac tune up x1, checked indoor unit for proper operations, unit is zoned upstairs and downstairs all dampers are opening and closing properly, Checked for amp draws and temperature split, media filter was recently changed last month. Unit has safety pan switch. Drain pan is clear. Outdoor unit found perfect refrigerant levels, checked electrical components and connections unit has turbo200x. Unit is also drawing higher amps than rated,