Job Checkin

System- Approx Age of System: 5yrs Refrigerant Type- R410a Metering Device- TXV SP/HP: 129/291 SLT/LLT: 58/80 VSAT/LSAT- 44/94 Superheat/Subcool- 13/13 Outdoor Entering Air Temp- 80 Outdoor Fan FLA- 1.1 Compressor RLA/LRA-10.9/ 91 Contactor Voltage-244/26 Capacitor Rating- 40.42/6.65 Indoor Return Dry Bulb Temp-72 Return Wet Bulb Temp-63 Supply Temp-54 Temperature Difference- 18 Required Difference- 16-18 Blower FLA-6.3 Filter Sizes – 20x25x4 Changed Filters – Y Blew out drain line: N (no blowout valve) Notes- Unit was operational on arrival. Checked filters. Checked operating pressures and temperatures. Checked indoor and outdoor electrical. Condenser capacitor is bad rated for 45/7.5mfd. Unit has no blowout valve. All other components showed no visible issues at this time. Recommend capacitor-(to ensure operation) and compressor saver-(to reduce amp and extend equipment life) Scheduled next tune up date: 10-21-20 8-10am