AC Diagnostic System: Back of warehouse Refrigerant TypeR410A Metering Device-TXV SP/HP SLT/LLT VSAT/LSAT SH/SC Outdoor Entering Air Temperature Returned tstat to original settings: Y Unit operational; prior to leaving: Y/N Notes: System that covers the back of the warehouse not working. System was locked out and showing code form VFD failure. Looked at the VFD and it was displaying code for over amping and system locked out. Reset system then checked motor. Motor drawing 9 amps and rated for 6.1 then the system locked out again. Loosened the fan belt as this should lower amp draw, reset and restarted system. The blower was still showing 9 amps. Determined that the motor has failed. Sending information to office to get an estimate written up and emailed over.