Ran water through the unit and all of the water drained out. I don’t believe this is a drain line issue at this time. I checked the pressures for both indoor units. I found the pressures are fluctuating from a VSAT of 28-38 degrees. This could be caused by a refrigerant issue or due to the blower wheel being dirty. Ms. Christ is going to order the mini split cleaning kit and clean the wheel. She is going to start documenting the times and temperatures to see if it happens more often. At this time it’s unclear as to why the unit is dripping on the inside. If the unit runs at a coil temperature of 32 degrees or below then the condensation will begin to freeze. After the unit that’s out then the ice will thaw out and this could overload the drain pan.