System-downstairs Approx Age of System: 2 years old Refrigerant Type- R410a Metering Device- TXV SP/HP:116/255 SLT/LLT:52/75 VSAT/LSAT-39/85 Superheat/Sub cool-13.7/9.0 Outdoor Entering Air Temp-86 Outdoor Fan FLA- 1.10 Compressor RLA/LRA-10.13/133.5. Rated 109 Contactor Voltage-244 Capacitor Rating-43.7/7.2 Indoor Return Dry Bulb Temp-73 Return Wet Bulb Temp-62 Supply Temp- 52 Temperature Difference- 21 Required Difference- 16-20 Blower FLA- 4.7 Filter Sizes – 20x30x1 Changed Filters – No clean Blew out drain line: Yes Notes- *everthing is cooling properly * condenser is pulling high amp draw upon start up, which can put strain on compressor and other components, would recommend hard start kit to lower amp draw upon start up. *customer approved to install compressor saver to reduce amp draw. System- upstairs Approx Age of System: 2 years Refrigerant Type- R410a Metering Device- TXV SP/HP:116/266 SLT/LLT:42/76 VSAT/LSAT-33/87 Superheat/