System- single system Approx Age of System: 12 Refrigerant Type- R410a Metering Device- TXV SP/HP: 129.2/374.1 SLT/LLT: 63.1/94.3 VSAT/LSAT- 44.5/111.5 Superheat/Subcool- 18.6/17.2 Outdoor Entering Air Temp- 90 Outdoor Fan FLA- .5 Compressor RLA/LRA- 8.1/39 Contactor Voltage- 242 Capacitor Rating- 42/4 Indoor Return Dry Bulb Temp- 67.2 Return Wet Bulb Temp- 42.5 Supply Temp- 53.6 Temperature Difference- 13.5 Required Difference- 16-20 Blower FLA- 6.1 Filter Sizes – 20x25x1/12x12x1 Changed Filters – Y (customer supplied) Blew out drain line: N (no service valve to blow out drain line) Notes- System has a high internal air pressure on the supply end, this high air pressure is causing a lot of moisture within the system so much that the unit is condensating in the attic. This high resistance in airflow and high moisture level in the supplying and has caused heavy corrosion over the evaporator coil that can lead to major refrigerant leak. Not only is this restrict