30045 FM 2978 Rd.
Magnolia, TX 77354
(281) 651-5484

Job Locations
for magnolia, tx


Map of Magnolia TX
Fernando G.

Fernando G.


Job Checkin

System- single system Approx Age of System: furnace 13 coil and condenser 3 Refrigerant Type- R410a Metering Device- TXV SP/HP: 124.2/348.3 SLT/LLT: 71/99.3 VSAT/LSAT- 42.4/106.3 Superheat/Subcool- 28.6/7 Outdoor Entering Air Temp- 93 Outdoor Fan FLA- .3 Compressor RLA/LRA- 10.2/84.1 (high energy draws on start up) Contactor Voltage- 240 Capacitor Rating- 21/2 (very weak capacitor can fail sometime soon) Indoor Return Dry Bulb Temp- 73.3 Return Wet Bulb Temp- 45.6 Supply Temp- 55 Temperature Difference- 18.5 Required Difference- 16-20 Blower FLA- 6 Filter Sizes – 20x25x1/12x24x1/12x12x1 Changed Filters – N Blew out drain line: Y Returned tstat to original settings: Y Unit operational; prior to leaving: Y Notes- Dual run capacitor is very low and value at this time high risk for potential failure in the future. Just replacing capacitor before failure, as well as including a compressor saver to reduce high energy jars on start up assisting the compressor and w