30045 FM 2978 Rd.
Magnolia, TX 77354
(281) 651-5484

Job Locations
for montgomery, tx


Map of Montgomery TX
Caleb J.

Caleb J.


Job Checkin

AC Diagnostic System: upstairs Refrigerant Type R22/R410A- R410A Metering Device-Fixed Orifice/TXV- TXV SP/HP- 138.7/293.1 SLT/LLT- 82.5/90.2 VSAT/LSAT- 48.8/94 SH/SC- 34.2/3.6 Outdoor Entering Air Temperature- 78 Notes: Arrived to customers home for water coming out of the emergency line outside. Found the primary drain line for the upstairs system clogged. The primary line terminates at the sink in the laundry room. Customer has signed up for a comfort club membership for both systems and approved installing a blow out valve and clearing the drain line in question. After clearing the drain line I checked refrigerant pressures and noticed that the superheat for the system is unusually high. Found that the 1” filter that services this area of the home is very dirty. I made the customer aware of it and he will be replacing it himself. System is operational at this time. . . . . .