System- trane Approx Age of System: 4 Refrigerant Type-R410a Metering Device- TXV SP/HP: 102/223/ SLT/LLT: 57/72 VSAT/LSAT- 36/76 Superheat/Subcool- 24/6 Outdoor Entering Air Temp- 64 Outdoor Fan FLA- .9 Compressor RLA/LRA- 4.9/58.8 Contactor Voltage- 238/25 Capacitor Rating- 45/7.5 actual 44.6/7.5 Indoor Return Dry Bulb Temp- 69 Supply Temp- 51 Temperature Difference- 18 Required Difference- 15-20 Blower FLA- 5.7 Filter Sizes – 20x25x4 Changed Filters – Y customer supplied Blew out drain line: Y Notes- performed ac tune up on system and unit is operating within manufactured specs. Did find that unit only has pan switch on but no blow out valve to clear line set and also no in line switch to prevent water from hitting pan. Also customer has a dehumidifier that also is tied to the primary line and no way to clear that or close it when clearing primary line. Suggest blow out valve on both units to keep them clear and a inline on unit to prevent water hitt