Job Checkin

System- single Approx Age of System: 4 Refrigerant Type- R410a Metering Device- TXV SP/HP: 118/243 SLT/LLT: 48/79 VSAT/LSAT- 38/81 Superheat/Sub-cool - 10/2 Outdoor Entering Air Temp- 73 Outdoor Fan FLA- 2.3 (after repair 1.4) Compressor RLA/LRA- 14.3/127.2 (rated limit-17.9/112) (After repair 9.0/67.3) Contactor Voltage-244.8 Capacitor Rating- 19/2 (45/5) Indoor Return Dry Bulb Temp- 70 Return Wet Bulb Temp- 61 Supply Temp- 52 Temperature Difference-18 Required Difference- Blower FLA- 3.0 Filter Sizes – Changed Filters – N Blew out drain line: N Notes- found unit incorrectly wired at the capacitor - fan common tied into the Herm terminal. This caused over amping on the unit fan and compressor. This coupled with the failing capacitor significantly increased noise levels. Replaced ru