Ernest P.

Ernest P.


Job Checkin

System- master Approx Age of System: 6 Refrigerant Type- / R410a Metering Device- TXV SP/HP: 129/280 SLT/LLT: 47/90 VSAT/LSAT- 44/91 Superheat/Subcool- 3/1 Outdoor Entering Air Temp- 81 Outdoor Fan FLA- 1.2 Compressor RLA/LRA- 6.3/31.7 Contactor Voltage- 240 Capacitor Rating- 40/7.5 Indoor Return Dry Bulb Temp- 68 Return Wet Bulb Temp- 59 Supply Temp- 50 Temperature Difference- 18 Required Difference- 17 Filter Sizes – 20x25x4 Changed Filters – N (Clean) Blew out drain line: N Notes- performed ac tuneup. System was operational upon arrival. No condensation protection. System- Main Approx Age of System: 6 Refrigerant Type- R410a Metering Device- TXV SP/HP: 122/292 SLT/LLT: 51/83 VSAT/LSAT- 41/93