System-main Approx Age of System: 10 years Refrigerant Type- R410a Metering Device- TXV SP/HP:134/348 SLT/LLT: 63/98 VSAT/LSAT- 46/105 Superheat/Subcool-17/7 Outdoor Entering Air Temp-93 Outdoor Fan FLA- 1.8 Compressor RLA/LRA-11/119 Contactor Voltage-241/24 Capacitor Rating-41 of 45 Indoor Return Dry Bulb Temp-77 Return Wet Bulb Temp-65 Supply Temp- 58 Temperature Difference-19 Required Difference-16-24 Blower FLA- 2.1 Filter Sizes – 20x30x1 Changed Filters – N Clean Blew out drain line: N no valve Returned tstat to original settings: Y Unit operational; prior to leaving: Y Notes-system is running within manufactured specs , no issues at this time. Will recommend a blowout valve though to allow drain line to be cleared if blockage occurs. Scheduled next tune up date: Thursday January 7th 12-4