System- 1 system house Approx Age of System: 3 years old Refrigerant Type- R410a Metering Device- TXV SP/HP:103/215 SLT/LLT:59/82 VSAT/LSAT- 37/88 Superheat/Subcool-22/6 Outdoor Entering Air Temp-71 Outdoor Fan FLA- 0.73 Compressor RLA/LRA-6.55/91.8. Contactor Voltage-246 Capacitor Rating-4.7/44.7 45/5 Indoor Return Dry Bulb Temp-73 Return air wet bulb- 63 Supply Temp- 56 Temperature Difference-17 Required Difference-15-20 Blower FLA- 2.7 Filter Sizes – 20x25x1. 12x12x1 Changed Filters – No (clean) Blew out drain line: No way to blow out drain lines Notes- System does not have any overflow protection to help prevent water damage to the ceiling. Then secondary drain line that is meant to redirect the water into the emergency drain pan is not over the pan so in the event of the primary drain backi