System- single system Approx Age of System: 5 Refrigerant Type- R410a Metering Device- TXV SP/HP: 114.9/223.5 SLT/LLT: 60.8/74.9 VSAT/LSAT- 38.5/76.4 Superheat/Subcool- 22.4/1.4 Outdoor Entering Air Temp- 69.1 Outdoor Fan FLA- .6 Compressor RLA/LRA- 6.5/ n/a system has a circuit board Contactor Voltage- n/a no contactor Capacitor Rating- 34/2 Indoor Return Dry Bulb Temp- 65.9 Return Wet Bulb Temp- 41.8 Supply Temp- 44.3 Temperature Difference- 21.6 Required Difference- 16-20 Blower FLA- 3.2 Filter Sizes – 20x25x4 Changed Filters – Y Blew out drain line: Y Notes- the condenser capacitor value tested and rated by the manufacturer is 40/5mfd +-5% at this time the capacitor is out of tolerance reading 34/2, since our last visit the value read 37.4/3.1mfd the capacitor value has dropped significantly. I recommen