Fernando G.

Fernando G.


Job Checkin

System- D/s system Approx Age of System: 11 Refrigerant Type- R410a Metering Device- TXV SP/HP: 111.7/301.3 SLT/LLT: 50.1/86 VSAT/LSAT- 36.9/95.9 Superheat/Subcool- 13/10 Outdoor Entering Air Temp- 78.3 Outdoor Fan FLA- 1.4 Compressor RLA/LRA- 11.2/138.7 Contactor Voltage- 247.3 Capacitor Rating- 68/6 Indoor Return Dry Bulb Temp- 68.8 Return Wet Bulb Temp- 43.4 Supply Temp- 49.9 Temperature Difference- 18.9 Required Difference- 16-20 Blower FLA- 8.1 Filter Sizes – 20x25x1/12x24x1 Changed Filters – N Blew out drain line: N Notes- system has heavy organic growth in the supply plenum at this time it doesn’t look like its reached the duct work but left untreated it will continue to grow and spread throughout the duct system. These organic growths not only affect the workings of the equipment but have a health affect on people with allergies and respiratory issues. Filters have been replaced recently no need to change them at this time, there is no service