Job Checkin

System- Bryant Approx Age of System:2 Refrigerant Type- R410a Metering Device- TXV SP/HP:126.6/272.9 SLT/LLT:52.3/80.5 VSAT/LSAT- 43.6/89.3 Superheat/Subcool-8.5/8.8 Outdoor Entering Air Temp-72 Outdoor Fan FLA- .9 Compressor RLA/LRA-10.5/ Contactor Voltage-243.4/25.1 Capacitor Rating-44.1/7.2 Indoor Return Dry Bulb Temp-71.4 Return Wet Bulb Temp-64.6 Supply Temp- 52.8 Temperature Difference-18 Required Difference-16-20 Blower FLA- 5.5 Filter Sizes –20x25x4(2)(still clean at this time) Changed Filters – N Blew out drain line: Y Notes-Upon arrival, checked in with Mrs.Kress and located hvac equipment. ,add the call for cooling and system came on accordingly. At the condenser, refrigerant pressures and electrical readings are within manufacture specifications. After taking readings