30045 FM 2978 Rd.
Magnolia, TX 77354
(281) 651-5484

Job Locations
for shenandoah, tx


Map of Shenandoah TX
Ken P.

Ken P.


Job Checkin

AC Diagnostic Site Contact: Roger System: Server room Refrigerant Type R410A Metering Device- EXV SP- 30 VSAT- -15 Outdoor Entering Air Temperature 85 Returned tstat to original settings: Y Unit operational prior to leaving: Y Notes: Server room unit not cooling. Found system low on refrigerant. Talked to Jeff and he authorized added 2 pounds of refrigerant. Found the leak with electronic leak detector in the Indoor coil. Will have office check warranty and send estimate for repair. Once he receives estimate Jeff will decide if we wants to proceed with repair or wait and see how long refrigerant lasts. After adding refrigerant Refrigerant Type R410A Metering Device- EXV SP- 122 SLT- 90 VSAT- 41 SH- 6 Outdoor Entering Air Temperature 85