Fernando G.

Fernando G.


Job Checkin

System- D/s system Approx Age of System: 10 Refrigerant Type- R410a Metering Device- TXV SP/HP: 117.1/254.1 SLT/LLT: 54.3/83.4 VSAT/LSAT- 39.4/84.4 Superheat/Subcool- 15.3/1.1 Outdoor Entering Air Temp- 76.1 Outdoor Fan FLA- .9 Compressor RLA/LRA- 7.8/92.3 Contactor Voltage- 241.5 Capacitor Rating- 41/7.5 Indoor Return Dry Bulb Temp- 66.8 Return wet bulb- 42.3 Supply Temp- 49.6 Temperature Difference- 17.2 Required Difference- 16-20 Blower FLA- 8.19 Filter Sizes – 20x25x1 Changed Filters – Y Blew out drain line: Y Notes- system reads low on refrigerant at this time condenser coils have heavy dust build up that may not allow proper heat exchange. A thorough chemical cleaning would allow the system to remove heat easily with out causing strain on the equipment, or affecting refrigerant readings. The system is starting up with high initial energy draws at this time the compressor saver is in need of replacement to reduce these high starts and strain on the compressor. Next Sc